Wire Ampacity Calculator
Look up the allowable ampacity for copper and aluminum wire sizes per NEC Table 310.16, with derating for ambient temperature and conductor fill.
Results
⚠️ Results are for informational purposes only. Verify against applicable codes and manufacturer specifications before use.
How to Calculate Wire Ampacity
What Is Wire Ampacity?
Ampacity is the maximum current (in amperes) that a conductor can carry continuously under the conditions of use without exceeding its temperature rating. Exceeding ampacity causes insulation to degrade, potentially leading to short circuits, arc faults, and fire. Every wire size has a rated ampacity listed in NEC Table 310.16, but the actual ampacity under real-world conditions may be lower due to temperature and bundling derating factors.
NEC Table 310.16 Explained
Adjusted Ampacity = Base Ampacity × Temp Derating × Conductor Fill Derating
Both derating factors multiply together. If either applies, the adjusted ampacity will be lower than the table value.
NEC Table 310.16 provides base ampacities at an ambient temperature of 30°C (86°F) for copper and aluminum conductors at 60°C, 75°C, and 90°C insulation ratings. Most new installations use the 75°C column.
Temperature Derating (NEC 310.15(B)(2)(a))
When ambient temperature exceeds 30°C, the wire cannot dissipate heat as effectively, so its ampacity must be reduced. For example, at 40°C ambient, a 75°C-rated conductor has a derating factor of 0.88 — a wire rated for 25A now only carries 22A.
Conductor Fill Adjustment (NEC 310.15(B)(3)(a))
When more than 3 current-carrying conductors are bundled in a conduit or cable, mutual heating reduces each conductor's capacity. The adjustment factors are: 4–6 conductors → 80%, 7–9 → 70%, 10–20 → 50%, 21–30 → 45%, 31–40 → 40%.
Worked Example
Scenario: 6 AWG copper (75°C base = 65A), ambient 40°C, 6 current-carrying conductors in conduit.
- Base ampacity: 65A
- Temperature derating at 40°C: 0.88
- Conductor fill derating (6 conductors): 0.80
- Adjusted ampacity = 65 × 0.88 × 0.80 = 45.76A
Even though the wire is rated for 65A, under these conditions you can only load it to ~46A.
Practical Tips
- Both derating factors apply cumulatively — a wire in a hot attic with many conductors in conduit can lose 50%+ of its rated ampacity.
- Neutral conductors carrying only unbalanced current from a 3-phase system are not counted as current-carrying. However, a neutral in a 2-wire circuit is counted.
- Equipment grounding conductors are not counted for derating when there's only one in the raceway.
- When derating reduces ampacity below the load, you must upsize the wire — no exceptions.
Code References
NEC 310.16, NEC 310.15(B)(2)(a), NEC 310.15(B)(3)(a)