Grounding Conductor Size Calculator
Size equipment grounding conductor per NEC Table 250.66 and NEC Table 250.122 for grounding electrode and equipment grounding conductors.
⚠️ Results are for informational purposes only. Verify against applicable codes and manufacturer specifications before use. Always consult a licensed electrician/HVAC contractor and your local AHJ (Authority Having Jurisdiction) before performing work.
Guides are drafted with AI assistance and reviewed by our editors.
Related Calculators
How to Size Grounding Conductors per NEC
GEC vs EGC — What Is the Difference?
The Grounding Electrode Conductor (GEC) connects the grounding electrode (ground rod, water pipe, concrete-encased rebar, etc.) to the grounding terminal of the service disconnect. It is sized per NEC Table 250.66 based on the largest service-entrance conductor. The Equipment Grounding Conductor (EGC) provides a fault-current path from equipment to the source and is sized per NEC Table 250.122 based on the overcurrent protection device rating.
NEC Table 250.66 — GEC Sizing
Rule: GEC size depends on the largest service-entrance conductor and the type of grounding electrode.
For ground rod, pipe, or plate electrodes: GEC need not exceed 6 AWG copper per NEC 250.66(A). For concrete-encased or ground ring electrodes: use the full Table 250.66 lookup.
NEC Table 250.122 — EGC Sizing
The EGC is sized based on the rating of the overcurrent protective device ahead of the equipment. For a main service, this is typically the main breaker rating. Common sizes: 100A → 8 AWG, 200A → 6 AWG, 400A → 3 AWG.
Worked Examples
Scenario 1: 200A service with a ground rod electrode.
- Electrode type: Ground rod → NEC 250.66(A) caps GEC at 6 AWG Copper
- EGC from Table 250.122 at 200A OCPD → 6 AWG Copper
Scenario 2: 200A service with a concrete-encased electrode.
- Estimated service conductor: 2/0 AWG (for 101-200A)
- NEC 250.66 table: 2/0 or 3/0 AWG conductor → 4 AWG Copper GEC
Practical Tips
- Ground rod/pipe/plate electrodes have a hard cap of 6 AWG copper — you never need a larger GEC for these electrode types, regardless of service size.
- Concrete-encased (ufer) and ground ring electrodes require larger GECs for higher service sizes, as they follow the full Table 250.66.
- The GEC minimum is 8 AWG copper per NEC 250.66 — but this only applies to non-rod electrodes.
- When multiple grounding electrodes are present, the GEC is sized to the largest electrode's requirement.
Code References
NEC 250.66, NEC 250.122, NEC 250.54